Know a company with years of records? Refer it and earn up to $100K
Building design reference

MEP Drawings and RVT Files: Types, Viewers, Clash Checks

What MEP drawings are and their types, what an RVT file is and how to view one, how MEP coordination and clash detection work, and who owns the model.

MEP stands for
Mechanical, electrical, plumbing
RVT file
Revit project.rfa is a family, .rte a template
Open exchange format
IFCISO 16739
Default clash test types in Navisworks
4
Rolled drawings, a hard hat and a tape measure in a site office
Short answer

MEP drawings show a building's mechanical, electrical and plumbing systems: ducts, pipes, power, lighting and the equipment they serve. Today most are views of a 3D model, often an Autodesk Revit project saved as an RVT file. MEP coordination combines each trade's model, and clash detection finds where a duct, pipe or tray would hit structure or another system before it is built.

  • MEP covers mechanical (HVAC), electrical and plumbing; piping in Revit includes fire protection.
  • An RVT file is a Revit project. A newer release's file will not open in an older release.
  • Clash detection finds hard clashes, clearance problems and duplicates before installation.
  • Who owns the model is set by the design and construction contracts, not by who holds the file.

What are MEP drawings?

MEP drawings are the part of a building's drawing set that shows its mechanical, electrical and plumbing systems. Mechanical mostly means heating, ventilation and air conditioning (HVAC). The drawings show where equipment sits, how ducts, pipes, conduit and cable tray are routed, what size they are and how the systems connect.

Design software groups the work the same way. Autodesk's Revit help has one section called "Mechanical, Electrical, and Plumbing (MEP)" for creating "mechanical, electrical, and piping systems", and it notes that in the model "piping includes plumbing and fire protection" (Revit help, MEP; Revit help, System Browser). People often call this toolset "Revit MEP".

What are the types of MEP drawings?

A set usually moves from the engineer's design drawings to the contractor's detailed drawings and then to a record of what was built.

TypeWhat it showsUsually made by
Mechanical (HVAC) plansDuct routes and sizes, air terminals, equipment locationsMechanical engineer
Plumbing plans and riser diagramsWater, drainage and vent piping, floor by floor and verticallyPlumbing engineer
Electrical power and lighting plansPanels, circuits, receptacles, fixtures, conduit and trayElectrical engineer
One-line (single-line) diagramHow power flows from the service to each panelElectrical engineer
Fire protection plansSprinkler mains, branches and headsFire protection engineer or contractor
SchedulesTables of equipment, fixtures and panels with their ratingsEach discipline
Coordination drawingsAll trades overlaid, with agreed routes and elevationsContractor's coordination team
MEP shop drawingsFabrication and installation detail for the actual products boughtTrade contractor or fabricator
As-built (record) drawingsWhat was installed, including field changesContractor

For shop drawings, the US federal construction contract clause gives a useful definition: drawings "showing in detail (1) the proposed fabrication and assembly of structural elements, and (2) the installation" of materials or equipment (FAR 52.236-21). Shop drawings are normally logged and reviewed as submittals; see the submittal log template.

What is an RVT file?

An RVT file is a project saved by Autodesk Revit, the building information modelling (BIM) program. Autodesk's developer guide lists the three main Revit file types: "a project file with the extension .rvt, a family file with the extension .rfa, or a template file with the extension .rte" (Autodesk). The project holds the building model; a family is a reusable component such as a pump or a light fixture; a template is a starting point for new projects.

On a typical job each discipline keeps its own RVT file. The MEP engineer links the architect's and structural engineer's models into the MEP model and draws the systems around them, so the plans, sections and schedules on the sheets are all views of that model.

One practical limit matters when files are exchanged: "Revit models are not backwards-compatible. When you create or modify a model using the current release of the software, you cannot open the model later using a previous release" (Revit help). Agree the Revit release at the start of a project.

How do you open or view an RVT file without Revit?

There are three common routes, depending on whether you need to look, to measure or to reuse the model.

  • A browser viewer. Autodesk runs a free online file viewer, and its cloud document tools list ".rvt (current and previous 4 releases)" among the files they can display (Autodesk). An older file may need to be upgraded by someone with Revit first.
  • An IFC export. IFC is "an openly documented standard for the exchange of data about a building or facility", standardised as ISO 16739 and maintained by buildingSMART International (Library of Congress). If the author exports IFC from Revit, many free viewers and other BIM tools can open it.
  • PDF sheets. For reading the drawings, a PDF set printed from the model is still the simplest thing to ask for.

An IFC or PDF export is a snapshot. The Revit families, parameters, system definitions and view settings stay in the RVT file.

How do MEP coordination and clash detection work?

MEP coordination is the process of fitting every system into the space the building allows. Each trade models its work, the models are combined, and the team meets, usually weekly, to agree who moves what. Clash detection is the software check that feeds those meetings.

Revit has a built-in check. Its Interference Check tool "can find intersections among a set of selected elements or all elements in the model", and Autodesk says to use it "to prevent conflicts and reduce the risk of construction changes and cost overruns" (Revit help). The same page notes that MEP fabrication parts are not included and that "the recommended workflow is to use Navisworks", Autodesk's model review program. Navisworks offers "four default clash test types" (Navisworks help).

Clash test typeWhat it findsMEP example
HardGeometry that actually intersectsA duct running through a steel beam
Hard (conservative)The same test with a more cautious intersection methodCatches near-certain hits a standard test may miss
ClearanceGeometry closer than a set distanceA pipe with no room left for its insulation
DuplicatesThe same object modelled twiceTwo copies of one valve in the same place

Clash detection example: four clashes from one coordination meeting

A fictional clash log for level 3 of an office building shows what the record looks like once the meeting has dealt with each item.

IDClashTypeDecisionStatus
C-031Supply duct 600 x 300 against steel beam at grid C4HardMechanical lowers the duct 150 mm and flattens it to 800 x 250Resolved
C-032Chilled water pipe 25 mm from cable tray; 50 mm needed for insulationClearanceElectrical shifts the tray 100 mm northResolved
C-033Sprinkler main through return duct in the corridorHardFire protection reroutes above the duct; request for information sent to the engineerOpen
C-034Two identical floor drains at one locationDuplicatesPlumbing deletes oneResolved

Fictional data. A move that changes cost or scope usually ends up in a change order; see the change order log template.

Who owns the MEP drawings and the Revit model?

The contracts decide, so read them before you reuse or share a model. Under the standard AIA forms, AIA explains, "copyright ownership of the Instruments of Service (which would include any portion or version of a model) resides with the individual or entity that created them", and the building owner receives a license to use them for the project (AIA Contract Documents guide). On that default, the MEP engineer owns its design model and the trade contractor owns its fabrication model.

Defaults are often changed. The same AIA guide notes it "has become common for owners to include language in their design services agreements whereby they may take ownership of the architect's Instruments of Service". Where two parties exchange files with no agreement between them, AIA publishes C106, which "serves as a licensing agreement between two parties who otherwise have no existing licensing agreement for the use and transmission of digital data, including instruments of service" (AIA).

A linked model also contains other firms' work: the architect's and structural engineer's models, and manufacturers' families. Holding a copy does not give you rights in those parts. This page is general information, not legal advice.

Common mistakes with MEP models and drawings

These cause most of the rework on coordinated projects.

  • Opening and saving a shared model in a newer Revit release, which locks out everyone on the older one.
  • Sending an RVT file without the linked models it depends on.
  • Running clash tests on everything against everything and drowning the team in results, instead of testing system against system.
  • Ignoring clearance: insulation, access for maintenance and hanger space do not show up as hard clashes.
  • Closing clashes in the log without updating the model.
  • Treating the design model as fabrication-ready. Shop drawings carry the detail that gets built.
  • Handing the model to a third party without checking the contract for who owns it.

Your Revit models with MEP are also a data asset

A coordinated model with its clash history records how engineers route real systems through real buildings, and why routes changed. AI data buyers have asked Origin for this from MEP engineers: Revit models with MEP. Origin Data Partners is an independent data partner that helps a firm find out whether its project archive fits such a request.

Check three things before any model is shared. First, the design contract: who owns the model and what the client may restrict, as described above. Second, other parties' content: linked architectural and structural models and purchased family libraries are not yours. Third, confidentiality and security: client names, site addresses and the layouts of sensitive buildings such as data centres, hospitals and government facilities may be restricted by contract or by law. This page is general information, not legal advice.

Related guides: licensing architecture firm drawings and BIM, selling construction project records, the submittal log template and the change order log template.

Does your company hold records like these? See what your data is worth.

Common questions

What does MEP stand for in construction drawings?

Mechanical, electrical and plumbing. Mechanical mostly means heating, ventilation and air conditioning. Fire protection piping is usually coordinated with the same set.

What is an RVT file, and what program opens it?

An RVT file is a project saved by Autodesk Revit. Revit opens it, in the same release or a newer one than the release that saved it. Browser viewers from Autodesk can display it without Revit.

Is there a free RVT file viewer?

Autodesk runs a free online file viewer in the browser, and its cloud document tools list RVT among supported files. Another route is to ask the author for an IFC export, which many free viewers open.

What is the difference between MEP design drawings and MEP shop drawings?

Design drawings come from the engineer and show the intent: routes, sizes and equipment. Shop drawings come from the trade contractor or fabricator and show how the actual products will be fabricated and installed.

What is clash detection in BIM?

A software check that finds where elements of combined models conflict, such as a duct passing through a beam. Navisworks has four default test types: hard, hard (conservative), clearance and duplicates.

What is the difference between a hard clash and a clearance clash?

A hard clash is geometry that actually intersects. A clearance clash is geometry that comes closer than a set distance, for example a pipe with too little room for insulation.

Who owns the Revit model on a building project?

The contracts decide. Under standard AIA forms the firm that created a model keeps the copyright and the owner gets a license to use it for the project, but many owners negotiate different terms.

Sources and further reading

What is your company’s data worth?

AI companies pay $20K to $5M for company records. Six questions, no files.